Franklin Fueling Systems · Automatic Tank Gauges & Leak Detection

EVO™ LLD

Stand-alone electronic line leak detection for 2, 3 or 4 pressurised lines

WhatsApp us
Franklin Fueling Systems EVO LLD line leak detection console

Overview

EVO™ LLD gives a site electronic line leak detection without a full tank gauge. It comes as a complete kit with its own console, a pressure transducer for each line, a needle valve kit and a 3.0 gph (11.4 lph) leak generator kit, ordered as EVO-LLDS/2, /3 or /4 for two, three or four lines. Every testing feature is included as standard, so there are no software options to add later.

Each transducer threads into the leak detector port of the submersible pump manifold. At setup, AUTO-LEARN® introduces a calibrated leak and records the pressure decay curve of that line, so the installer never types in pipe lengths or diameters. Because the learned values cannot be edited by hand, staff cannot alter setup data to clear an alarm.

In service the console runs a 3.0 gph gross test after every dispense cycle or 45 minutes and shuts down the pump if it fails. Precision tests run while line temperature is stable, at 0.2 gph once a month and 0.1 gph once a year, and Statistical Line Leak Detection (SLLD) gathers pressure data during normal trading so that busy sites with few quiet periods can still reach 0.2 gph precision. Alarms show on the console screen and can be pushed by email or SMS through PRO™ Connect.

Apex supplies, installs and services EVO™ LLD kits in Lebanon, including transducer fitting and AUTO-LEARN® setup.

Key features

  • Complete kits for 2, 3 or 4 lines with console and pressure transducers
  • AUTO-LEARN® setup with no manual entry of pipe data
  • 3.0 gph gross test after each dispense or 45 minutes, with pump shutdown
  • Precision line tests at 0.2 gph each month and 0.1 gph each year
  • SLLD statistical testing for sites that rarely stop fuelling
  • Works with pumps producing 25 psi (1.7 bar) or more
  • Monitors flexible, steel and fiberglass lines in any combination
  • Transducer cable runs of up to 1,500 ft (457.2 m) to the console

Specifications

EVO™ LLD technical data

EVO™ LLD specifications (Franklin datasheet FFS-0987)
ParameterValue
Transducer dimensions4 in (102 mm) x 2 in NPT
Operating temperature-40° F to 149° F (-40° C to 66° C)
Operating pressure0 to 100 psi (0 to 6.89 bar)
Transducer cable10 ft (3.0 m) three conductor cable with shield and polyurethane jacket
Max cable length1,500 ft (457.2 m) transducer to console
Sensor port fitting2 in (51 mm) female NPT
Sensor materialAnodized aluminum body and stainless steel sensor
ApprovalsUL, cUL, ATEX, IECEx; third-party certified leak detection
EVO™ LLD kits
ModelDescription
EVO-LLDS/22-line kit with console and (2) pressure transducers
EVO-LLDS/33-line kit with console and (3) pressure transducers
EVO-LLDS/44-line kit with console and (4) pressure transducers

Figures from the manufacturer's published documentation. Confirm the final configuration with Apex at quotation stage.

Questions

EVO™ LLD: common questions

Does EVO™ LLD need an EVO™ tank gauge?
No. It is a stand-alone kit with its own console. Sites with an EVO™ 600 or 6000 can use the integrated ELLD software option instead.
What pump pressure is needed?
The submersible pump must generate 25 psi (1.7 bar) or more.
Which fuels can the transducers handle?
Franklin lists diesel and biodiesel blends (B5, B6 to B20, B99 to B100), gasoline up to E10, and ethanol blends E15 to E20 and E51 to E83.

Request a Quotation

Get a quotation for the Franklin Fueling Systems EVO™ LLD.

Tell us the quantities and the site. Apex prepares every quotation for the project, then supplies, installs and services the equipment in Lebanon.

WhatsApp us